Servicing and spares | 39
6 720 ... ... (YYYY/MM)Product Name
– CO
2
is less than 0.2%
If the readings are outside these limits then this indicates that there
is a problem with the flue system or combustion circuit, e.g. missing
or dislodged seals
Fig. 51 Flue integrity test
10.4 Service inspection - Component access
Remove the boiler front panel to gain access to components.
Pull the top corners of the front panel away from the case until the
ball catches are released.
Lift the panel off the two lower brackets and set the panel aside.
Lower the control panel into the service position.
Remove the four screws securing the combustion chamber cover and
remove to gain access to the components.
Fig. 52 Component access
10.4.1 Control panel - Service position
To lower the control panel into the service position, remove one top
screw [1] from each side of the mounting bracket, loosen the bottom
screws slightly and pivot the panel forward. The control panel is
supported at approximately 100 °.
Fig. 53 Control panel to the service position
10.5 CHECKING THE GAS INLET PRESSURE
Refer to section 7.5 and check that the gas working pressures in the
system conform to within the figures shown below:
6720809859-23.1Wo
NOTICE: Gas inlet pressure
Ensure that the gas pressure is satisfactory with all
other gas appliances working.
Do not continue with the other checks if the correct
gas pressure can not be achieved.
6720809859-18.1Wo
1
6720809859-19.1Wo

Table of Contents