Setting Up Points and Outputs
Using the Relay Option Within Point Assignments
Relay Programming allows any one point or several points to latch a single relay through
software when the selected point generates an alarm. Relays are number 1 through 8 and are
programmed by entering the number of the relay (1 - 8) in the Relay column in Point
Assignments. This relay latches on a generated alarm and resets after acknowledging and then
clearing the alarm from memory.
Relay D8129 Actual Relay Number
D7412GV4
1
D9412GV4
2
1 9 73
2 10 74
3 11 75
4 12 76
5 13 77
6 14 78
7 15 79
8 16 80
1
For the D7412GV4, connect to Terminal 28 for data (Zonex 1 Out)
2
For the D9412GV4, connect to Terminal 26 for data (Zonex 2 Out).
Table 7.1: Actual Relays Latched by Control Panel Type
Switch Number Setting
1 ON
2 OFF
3 ON
4 ON
Table 7.2: D8129 Switch Settings for All Control Panel Types
Notice!
Programmers must be aware of the following considerations:
Do not use relays designated within Point Assignments for multiple functions. For example,
Relays 73 through 80 on the D9412GV4 should not be used for relay-follow-point or area-wide
or panel-wide relays.
Relays should not be selected to follow points programmed as Invisible Points.
7
7.1
Control Panel Setting Up Points and Outputs | en 17
Bosch Security Systems, Inc. Quick Reference Guide 2014.05 | 05 | F.01U.265.463