Point Index (Default Values)
Pt Index
Number
Description Pt Index
Number
Descriptions
1 24-hr Instant Open/Short 17 Gas
2 24-hr Inv/Sil on Short 18 Gas: Supervisory
3 Pull Station 19 Aux AC Supervision
4 Smoke Detector 20 Part On: Watch Off
5 Smoke Detector w/
Verification
21 Part On: POPIT Motion
6 Bell Supervision 22 Fire Supervisory on Open
7 Part On: Instant 23 Non-Fire Supervisory Op
8 Part On: Delay 24 Local: Buzz on Fault
9 Prt: Inst Local:Dis 25 Prt: Delay
10 Interior: Instant 26 Part On: Instant
11 Interior: Delay 27 Part On: Delay
12 Int: Inst Local: Dis 28 Interior: Follower
13 Interior: Follower 29 Interior: Instant
14 Maintained Keyswitch 30 Interior: Delay
15 Momentary Keyswitch 31 24-hr Instant Open/Short
16 Open/Close on Fault
Table 7.3: Point Index Numbers and Descriptions
Notice!
The default indexes are not always the best selection. If you experience unwanted trouble
conditions, refer to the Point Response Selections table and make any necessary adjustments.
Inovonics EchoStream Wireless points produce a Short when faulted and an Open for a
tamper.
Description Description
24-Hour Open/Close Point
Part On Fire Point
Interior Aux AC Supervision
Interior Follower Gas Point
Keyswitch Maintained Custom Function
Keyswitch Momentary
Table 7.4: Point Type Selections
7.2
18 en | Setting Up Points and Outputs Control Panel
2014.05 | 05 | F.01U.265.463 Quick Reference Guide Bosch Security Systems, Inc.