Panel event Modem4 code
D6500 mode
Modem4 code
Bosch SIA
mode
Contact ID event Contact ID code
Time Changed by Receiver
Sync
NsD07 Nid5001JT Time/Date Reset 1 625 00 F01
Time Changed by User NsD07 NidiiiiJT Time/Date Reset 1 625 00 uuu
Trouble Tspppp NriaaBTpppp Sensor Trouble 1 380 aa ppp
Trouble with Ground Fault Tpppp NriaaBTpppp Ground Fault 1 310 01 000
Unverified Event Kpppp NriaaUGpppp Cross-Zone Trouble 1 378 aa ppp
User Authority level has
changed
NsD40 NidiiiiJZiiii Local Only Local Only
User Passcode Tamper – Too
Many Attempts
NsD03 NriaJA Wrong Code Entry 1 461 aa 000
Walk Test End RsssF Nriaa/idiiiiTE Walk Test Mode 3 607 aa uuu
Walk Test Start TsssF Nriaa/idiiiiTS Walk Test Mode 1 607 aa uuu
Watchdog Reset NsD09 NpiddddYW System Reset 1 305 00 000
Watchdog Reset – SDI Device
Reported identifies the
Source
NsD09 NpiddddYW System Reset 1 305 00 000
SDI/SDI2 Address Information
Notice!
All point numbers, user ID’s, output numbers, and device identifier numbers are formatted as
4-digit numbers (right justified with zero’s) when transmitted from the control panel in
Modem4 format.
SDI/SDI2 Bus Address zzz Data Values Description
1-16 001-016 SDI Keypad 1 through 16
33-40 033-040 Access Module 1 through 8
80 080 SDI Automation Module1
88 088 SDI Network Module 1
92 092 SDI Network Module 2
2-25 201-224 SDI2 Octo-input Modules 1 through 24
66-77 301-312 SDI2 Octo-output Modules 1 through 12
151 801 SDI2 Premises RF Module
161-168 851-858 SDI2 RF Repeater 1 through 8
173 401 SDI2 Network Module 1
11.2
Control Panel Reporting and Device Number Information | en 35
Bosch Security Systems, Inc. Quick Reference Guide 2014.05 | 05 | F.01U.265.463