Reporting and Device Number Information
Reporting Format Definitions
Notice!
The GV4 (v2.xx and higher) send 4-digit user and point numbers. Panels using Modem4 send
4-digit Point and User data.
Panel event Modem4 code
D6500 mode
Modem4 code
Bosch SIA
mode
Contact ID event Contact ID code
A point supervisory condition
occurred
Jspppp NriaBSpppp 24 hour Non-Burglary 1 150 aa ppp
A valid local RPS access
occurred
RsF01 NLS Successful Download/
Access
1 412 00 000
A valid remote RPS access
callback occurred
RsssF NphhhRS Successful Download/
Access
1 412 00 000
A valid remote RPS access
occurred
RsssF NRS Successful Download/
Access
1 412 00 000
AC Fail – mains power supply Pssss NAT AC Loss 1 301 00 000
AC Restore – mains power
supply
Rsss0 NAR AC Loss 3 301 00 000
Access Denied – Door
Secured
ADpppp Nriaa/
idiiiiDZpppp
Access Denied 1 421 aa uuu
Access Denied – interlock ADpppp Nriaa/
idiiiiDZpppp
Access Denied 1 421 aa uuu
Access Denied – No rights in
area by card
ADpppp Nriaa/
idiiiiDVpppp
Access Denied 1 421 aa uuu
Access Denied – No rights in
area by passcode
ADpppp Nriaa/
idiiiiDVpppp
Access Denied 1 421 aa uuu
Access Denied – Unknown ID ADpppp Nriaa/DDpppp Access Denied 1 421 aa uuu
Access Granted AGpppp Nriaa/
idiiiiDGpppp
Access Report by User 1 422 aa uuu
Add Card to a User NsD30 NidiiiiDAiiii Local Only Local Only
Add Key Fob to a User
(Assign Card Event)
NsD30 NidiiiiDAiiii Local Only Local Only
Alarm Aspppp NriaBApppp Burglary 1 130 aa ppp
Alarm Cross Point Aspppp NriaBMpppp Burglary 1 130 aa ppp
Alarm Exit Error Aspppp Nria/idiiiiEApppp Entry/Exit 1 134 aa ppp
Alarm with Recent Closing Aspppp Nria/CRpppp Entry/Exit 1 459 aa uuu
11
11.1
26 en | Reporting and Device Number Information Control Panel
2014.05 | 05 | F.01U.265.463 Quick Reference Guide Bosch Security Systems, Inc.