The Point Response Selections table indicate:
– D = Delayed Response
– I = Instant Alarm
– S = Supervisory
– T = Trouble
– Blank = No Response
To make a custom point index, use the Point Type Selection table and Point Response Selections
table. For example, to create an inferior Follower point with a delay on Open and Trouble on
Short, use Point Type 3 and Point Response 5.
Point Response
Selection*
0 1 2 3 4 5 6 7 8 9 A B C D E F
Turned on
(armed)
Open I I I I D D I I D I I I I I T
Short I I I I I I D D D I I I I I I
Turned off
(disarmed)
Open T T T I I T I T
Short T T T I T I I
24-Hour Open I T I T I T S T S S N/A
Short I I T T I T T S S S
*Selections: D = Delayed Response, I = Instant Alarm, S = Supervisory, T = Trouble, B = No
Response
Table 7.5: Point Response Selections*
Control Panel
Setting Up Points and Outputs | en 19
Bosch Security Systems, Inc. Quick Reference Guide 2014.05 | 05 | F.01U.265.463