D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
.
Bosch Security Systems, Inc. | 11/05 | F01U011024B 21
Figure 14: Switch D9210B Location
Control Panel
Door #3 Door #2
Disconnect known good D9210B from
current location and reconnect it in place
of affected D9210B (set aside).
D9210B
for Door #3
1
PWR +
7
SDIB
6
SDIA
5
COM
8
T +
10
ZN +
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
13
REX
12
COM
11
RTE
16
DATA 1
17
BUZZER
18
LED
15
DATA 0
14
+5.20V
D0
READER
OPER
MON
1
2
3
4
5
6
ON
TTP5: SDI Fail 33 to 40
Description
The SDI Fail 33 to 40 error message appears at the
central station. The keypad shows SERVICE 9210.
Procedure
Refer to
TTP4 Keypad Shows SERVICE 9210 on page 18.
TTP6: Control Panel Log Shows “No
Entry” for Alleged Valid Card
If you just programmed the control panel, it might take
approximately 15 min for all programming changes to take
effect. Reset the control panel when the programming
session completes. If you are using RPS, ensure that you
select “Reset Panel” when you disconnect RPS from the
control panel.
Initial Actions
Ensure that the access card(s) are compatible with the
installed card reader. The card type should be 26-bit
Wiegand. Refer to
Table 3 on page 8 for a list of
compatible card types.
Procedure
At the keypad closest to the card reader, press
[CMD][5][6]. Enter a valid passcode if necessary. Create a
test user by selecting an unassigned user number.
D1255 Keypad: Press [NEXT] when the keypad shows
ADD PASSCODE? Press [ENT] when keypad shows ADD
CARD? Present a new access card to the card reader
when the keypad shows PRESENT CARD.
D1260 Keypad: Press [Continue]. Press [Passcode]. Press
[Card][Yes]. Present a new access card to the card reader
when the keypad shows Present Card.
If the keypad shows D9210B NOT READY, refer to
TTP7 on page 22.
Does the keypad show CARD IN USE?
In programming, go to the Users section and locate
the test user.
RADXUSR 1 programs Users 000 to 124.
RADXUSR 2 programs Users 125 to 249
(D9412GV2 only).
Record the site code and card data information from
the test user, and then delete the test user. Locate
the user with the affected access card, and replace
the site code and card data information with the test
user site code and card data information. Retest the
access card.
Locate the D9210B for the appropriate access door. Use
Table 8 on page 16 to match the D9210B’s DIP switch
address to the corresponding door number. Using RPS
software or your D5200 Programmer, go to
RADXAXSDoor Profile. Obtain the Entry Area setting for
the identified door. Go to RADXUSR1/USR2User
Number. Locate the user number assigned to the card.
Does the affected user have an assigned authority level
in the entry area for the identified access door?
Do any cards work at the identified door?
A B C