D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
.
Bosch Security Systems, Inc. | 11/05 | F01U011024B 23
TTP9: Access Door Does Not Relock after
Clearing a Fire Alarm and Resetting
the Control Panel
TTP8: Access Door Unlocks When Area Is
Disarmed
Description
Description
When the Auto Door programming prompt is set to
Yes, the access door locks when the area is armed, and
unlocks when the area is disarmed. Set this prompt to
No.
This is normal operation for the control panel.
Unlocked access doors must be manually relocked.
Procedure
Procedure
1. At a keypad, press [COMMAND][4][6]. Enter a
valid passcode if needed.
1. Identify the door number that unlocks when
disarming by locating the appropriate D9210B
and reading its DIP switch address. Refer to
Table 14.
2. If using a D1255 keypad, when CYCLE DOOR?
appears on the display, press [NEXT] once.
3. Using either a D1255 or D1260 keypad, select
UNLOCK DOOR.
The display shows UNLOCK: U U U U U U U U.
2. In programming, select RADXAXS→Door
Profile. Select the door identified in Step 1.
3. Change the Auto Door prompt from Yes to No.
- If the door is locked, the door’s number
appears.
4. Exit programming, then test the affected access
door.
- If the door is unlocked, “U” appears in the
door number’s place.
Table 14: D9210B DIP Switch Addresses
Door Controller Address
Device 1 2 3
D9210B #1
ON ON ON
D9210B #2 OFF
ON ON
D9210B #3
ON
OFF
ON
D9210B #4 OFF OFF
ON
D9210B #5
ON ON
OFF
D9210B #6 OFF
ON
OFF
D9210B #7
ON
OFF OFF
D9210B #8 OFF OFF OFF
- If a door is not active, “--” appears in the door
number’s place.
The D9412GV2 supports up to eight
doors; the D7412GV2 supports up to four
doors.
4. To relock an unlocked access door, enter the door
number and press [Enter]. The “U” changes to the
door’s number.
5. Press [MENU/ESC] until the idle text appears.