D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
22 Bosch Security Systems, Inc. | 11/05 | F01U011024B
A B C
Using RPS software or your D5200
Programmer, go into GV2MAINUser
InterfaceAuthority LevelsAuthority Level
1Security Level (Access Level). Ensure that
this prompt is set to “M.” Refer to Table 12 for
more information.
The authority level used is for test
purposes only. See customer for preferred
authority level assignment.
In RADXUSR1/RADXUSR2, locate the user
number assigned to the affected card. Assign
an authority level of 1 in the entry area
assigned to the access door.
Obtain the user number of a card that works. Identify
the authority level for the entry area assigned to the
access door. Assign this authority level to the entry
area assigned to the access door for the affected
card.
1. Using RPS or the D5200 Programmer, go to
GV2MAINFunction List.
2. Find a menu item with a blank function number.
3. Enter Function 37 into that menu item.
4. Enable the new menu item by changing it from “No” to
“Yes” for all connected keypads.
5. Send the programming changes to the control panel.
6. Using any keypad connected to the control panel,
press [MENU], then press [NEXT] until CHANGE
LEVEL? appears. Press [ENT].
7. The keypad shows ACCESS LEVEL CTL. Enter the
authority level assigned to the user in the entry area of
the affected access door. Press [ENT].
Does the keypad show LEVEL # DISABLE?
The keypad shows LEVEL # ENABLE. Press [ENT] to
enable the level.
Replace the D9210B.
Table 12: Authority Level Assignments
Assignment Description
M User with this authority level can gain
access in any arming state.
P User with this authority level can gain
access only when the system is Perimeter-
armed.
D User with this authority level can gain
access only when the system is disarmed.
Blank No access is allowed regardless of
system’s arming state.
TTP7: D9210B NOT READY Appears on
Keypads When Enrolling Cards, Tokens, or
Keyfobs
Description
The D9210B that supervises the affected access door
does not have the correct door number programmed.
Procedure
1. Identify the keypad you are using by removing the
front cover and reading the DIP switch address.
Refer to
Table 13.
2. Identify the door number you are trying to enroll
cards at by locating the appropriate D9210B and
reading its DIP switch address. Refer to
Table 14
on page
23.
3. In programming, select GV2MAINCommand
CenterCmd Ctr AssignmentAssign Door.
4. For the command center identified in Step 1, enter
the door number identified in Step 2.
5. Exit programming and enroll cards, tokens, or
keyfobs.
Table 13: Command Center Address Settings
Switch
Address 1 2 3 4 5 6
Adr #1
ON ON ON ON ON
Adr #2 OFF
ON ON ON ON
Adr #3
ON
OFF
ON ON ON
Adr #4 OFF OFF
ON ON ON
Adr #5
ON ON
OFF
ON ON
Adr #6 OFF
ON
OFF
ON ON
Adr #7
ON
OFF OFF
ON ON
Adr #8 OFF OFF OFF
ON
Encoding Tone
ON/OFF
ON