D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
58 Bosch Security Systems, Inc. | 11/05 | F01U011024B
TTP17: Point 8 has an EOL Resistor and
Indicates a Short
TTP19: Points 128 and 248 Are Missing
Description
Procedure
Points 128 and 248 are the COMMAND 7 and
COMMAND 9 keypad panic points, respectively. If
these programmed points are enabled by assigning a
point index to them in RADXPNTS programming,
they appear as missing in View Point Status.
Refer to
TTP16 Point Trouble on One of the Eight On-board
Points
on page 57.
Pay particular attention to the suggested
Initial Actions.
Procedure
This is normal control panel behavior. These points
appear as missing because there is no hardware
associated with them. No corrective action is required.
TTP18: Control Panel’s On-board Point Has
Only an EOL Resistor Connected,
and the Keypad Indicates the Point
Is Faulted
Procedure
Refer to
TTP16 Point Trouble on One of the Eight On-board
Points
on page 57.