D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
56 Bosch Security Systems, Inc. | 11/05 | F01U011024B
Table 31: Point Type and Point Response Selections
Point Response
Point Type Selections 0 1 2 3 4 5 6 7 8 9 A B C D E F
1
Selections
24-Hour Open
0 6 O/C Point I I I I D D I I D I I I I I T
2
Armed
D279 (O/C Non-Priority) 1 Perimeter 7 Short I I I I I I D D D I I I I I I
D279 (O/C Priority) 2 Interior 8 Open T T T I I T I T
2
Disarmed
Easikey 3 Interior Follower 9 Short T T T I T I I
Keyswitch Maintained 4 Open I T I T I T S T S S
Not
Applicable
24-Hour
3
Short I I T T I T T S S S
5 Keyswitch Momentary
1
Selections: D = Delayed Response, I = Instant Alarm, S = Supervisory,
T = Trouble, Blank = No Response
2
For point types 1 through 3 only.
3
For point type 0 only.
Figure 29: D9210B Wiring
1
PWR +
7
SDIB
6
SDIA
5
COM
8
T +
10
ZN +
9
ZNCOM
2
LCKN/C
3
LCKCOM
4
LCKN/O
13
REX
12
COM
11
RTE
16
DATA 1
17
BUZZER
18
LED
15
DATA 0
14
+5.20V
1
2
3
4
1 - D9210B Access Control Module
2 - Tamper switch (normally open)
3 - Door contact (normal end-of-line [EOL] resistor in circuit)
4 - RTE/REX (normally open)