5.2.9
Instructions for Use
DG000066v01_nn.f
h11
Fig.5-16:
DC
Bus Connection With Contact Bars
Notes
on
Installation
If
in
special cases it
is
not possible to use the contact bars provided to establish
the connection, the connection must
be
established using the shortest possible
twisted
wires.
NOTICE
Risk
of
damage
by
reversing
the
polarity
of
the
DC
bus
connections
L+
and
L-
Make sure the polarity
is
correct.
Length of twisted wi
re
Line cross section
Line protection
Dielectric strength of single
strand against ground
Fig.5-17·
Ground
Connection
DC
Bus Line
Max.
2m
Min. 10 mm
2
,
but not smaller than cross section of supply feeder
By means of fuses
in
the mains connection
;::
750 V
(e
.g
.:
strand
type-
H07)
The ground connection of the housing
is
used to provide functional safety
of
the drive controllers and protection against contact
in
conjunction with the
equipment grounding conductor.
Ground the housings of the drive controllers:
1.
Connect the bare metal back panel
of
the drive controller
in
conductive
form to the mounting surface
in
the control cabinet. To do this, use the
supplied mounting screws.
2.
Connect the mounting surface
of
the control cabinet
in
conductive form to
the equipment grounding system.
3. For the ground connection, observe the maximum
allowed ground resist-
ance.