Rexroth lndraDrive Drive Controllers Power Sections HCS02
Instructions for Use
5.2.10
Shield
Connection
See Project Planning Manual of the drive system (index entry "Mains con-
nection
- Project planning").
XS1,
Shield
Connection
Control
Lines
NOTICE
Property
damage
due
to
temperatures
higher
than
105
°C!
Observe the indicated minimum distances!
Above the devices there may
only
be
such materials which
are not combustible
are insensitive to the occurring high temperatures
~
Always connect the shields with the largest possible metal-to-metal
contact surface.
XS1
i...
-:1
DG000099v01 _nn.
FH11
Fig.5-
18
:
Shield Connection XS1 (Control Lines)
Function
Connection point for the shields of lines connected to the control section and
of
which the connectors do not have their own shield connection.
XS2,
Shield
Connection
Motor
Cable
NOTICE
Risk
of
damage
to
the
drive
controller
by
too
long
screws!
Exclusively use screws of a
maximum
length
of
12
mm
for the thread of shield
connection XS2.
The connection consists
of
an
M6 thread and
is
used for mounting the fixing
device for
shield connection of the motor cable.