HCS02
5.2.8
1
Fig.S-14:
1
Lines to control voltage supply
Control Voltage Supply
at
X13
Instructions for Use
DGDDDD85v01_nn
_
FH1
1
The input
OV
is connected
in
conductive form to the housing po-
tential. It is therefore impossible to use
an
insulation monitor at
+24V and
OV
against housing.
L +
L-,
DC
Bus
Connection
-
!ffhiMII~a.
Lethal
electric
shock
caused
by
live
parts
with
more
than
50
V!
Before working
on
live parts: De-energize the installation and secure the power
switch against unintentional or unauthorized re-energization.
Wait at least
30
minutes
after switching off the supply voltages to allow dis-
charging. To shorten the waiting time until voltage has fallen below
50
V, you
can use a discharging device (see chapter "Appendix").
Check whether voltages have fallen below
50
V before touching live parts!
Function,
Pin
Assignment
The DC bus connection connects
• several drive controllers to one another