HCS02
EMC Measures for Design and Installation
Badly grounded control cabinet doors act as antennas. Therefore, connect the
control cabinet doors to the cabinet on top,
in
the middle and on the bottom via
short equipment grounding conductors with a cross section of at
least 6 mm
2
or, even better, via grounding straps with the same cross section. Make sure
connection points have good contact.