28/36 Digital axis control VT-HMC...1X | Operation
Bosch Rexroth AG, Edition 01.2021, RE 30239-B
9 Operation
A prerequisite for the function of the VT-HMC...1X is its parameterization
and programming (→ creation of the PLC application) using the software
IndraWorksDs or IndraWorks MLD.
9.1 DIAGNOSTICS
The software IndraWorks offers users comprehensive diagnostic options.
Moreover, the VT-HMC...1X features an error and diagnostic message memory, in
which the errors occurred last are logged. This memory can be evaluated by means
of the IndraWorks software.
During operation, LEDs signal the operating states:
Status LED Indication status
Module (MS)
Off No voltage supply
Flashing green/red Initialization
Flashing green Parameterization mode active
Green Operating mode active
Flashing orange Warning
Flashing red Error
Permanently lit red Exception
Status LED Indication status
Network (NS)
Off No voltage supply
Green Operation
Status LED Indication status
SD card (SD)
Off No SD card available
Flashing green SD card not ready for operation
Green SD card available and ready for operation
Status LED Indication status
Digital inputs (Di1 through Di8)
Off Input logical “0“
Green Input logical “1“
Digital outputs (Do1 to Do4, V_ANA and V_SSI)
Off Output logical “0“
Orange Output logical “1“
Status LED Indication status
PROFIBUS (PB)
Off Bus not active
Green Bus in “Data_Exchange“ state