● Install the control only horizontally on a mounting rail attached to a wall
● Keep the maximum distance possible from interference sources
● Provide the following minimum distances for sufficient cooling:
30 mm
30 mm
100 mm
100 mm
122.7
126.3
100
30 mm
Fig. 10-3: Minimum distances for the circulation of ambient air
In case of a several line design, the supply air has to be measured under each
line and its limit value has to be observed. For information on ambient tem-
peratures, refer to chapter 6 "Ambient conditions" on page 7
● Additionally, provide sufficient distance for mounting, demounting, plugs and
cables.
For more information on mounting, demounting and connecting lines, refer to
the application description "IndraControl S20: System and Installation", part no.
R911335990.
18/69
Mounting, demounting and electric installation
IndraControl XM21, XM22 Controls
Bosch Rexroth AG R911340667_Edition 04