Fig. 12-5: Reset button
Press the "Reset" button at running control to trigger a voltage cycle (reset).
The "Reset" button is provided with two functions triggered when the reset but-
ton is pressed while applying the supply voltage:
● Press the "Reset" button < 5 seconds: Triggering the fallback mode (see chap-
ter 12.5 "Fallback and recovery" on page 54).
● Press the "Reset" button > 5 seconds until the LEDs DIA3 and DIA4 flash alter-
natingly: Triggering the initial firmware (see chapter 12.2 "XM2x initial firm-
ware" on page 39).
The "Reset" button can only be actuated with a sharp tool (e. g. pen-
cil).
12.2 XM2x initial firmware
The control variant "XM2x00.01" is delivered with initial firmware.
The initial firmware provides commissioning and maintenance functions. Basic
functions can me activated manually without any additional tools, see chapter
12.2.3 "Starting and opening the initial firmware" on page 41. The XM2x pro-
vides a simple interface with its operation mode switch SF1 and the LED display
panel.
The commissioning tool "IndraControl First Touch" (see chapter 12.3
"IndraControl First Touch" on page 43) provides a more comfortable operation