11 Maintenance 11
11.5.7 Disposal Vessel with Overfill Sensor (Optional Equipment)
You must check the function of the overfill sensor once a week.
Sequence of the check:
- Loosen the 2" screwed union
- Lift the ventilation pipeline
- The light-emitting diode (LED) on the probe is green
- Now touch the probe at the tip (3 - 5 cm/1.2 – 2 inches); the color of the LED must change from
green to red.
- The probe is in order
- Firmly tighten the 2" screwed union again