Parameter
Notation
Parameter
Description
Range
Default
Value
Register
Address
Data
type
2
Alarm 2 function
ALF2
0 : Process high alarm
1 : Process low alarm
2 : Deviation high alarm
3 : Deviation low alarm
4 : Deviation band
high/low alarm
62
5 : End of profile alarm
6 : Hold mode alarm
7 : Static mode alarm
Alarm 2 operation
mode
Low: 0.1
High:
50.0 C
(90.0 F)
L
L
0.1 C
(0.2 F)
L
L
Hysteresis control
for alarm 2
A2MD
A2HY
63
64
65
2 : Deviation high alarm
3 : Deviation low alarm
4 : Deviation band
high/low alarm
Alarm 3 function
(for P41 only)
0 : Process high alarm
1 : Process low alarm
2
ALF3ALF3
66
5 : End of profile alarm
6 : Hold mode alarm
7 : Static mode alarm
Alarm 3 operation
mode
(for P41 only)
A3MD
67
R/W
R/W
R/W
R/W
R/W
Reserved
UM0P411A
0
0
24
0 : Normal alarm action
1 : Latching alarm action
2 : Hold alarm action
3 : Latching & hold
alarm action
0 : Normal alarm action
1 : Latching alarm action
2 : Hold alarm action
3 : Latching & hold
alarm action