Chapter 3 ConfigurationChapter 3 Configuration
3-1 Password3-1 Password
The parameters stored in Home page can be obtained by pressing
scroll key . The parameters stored in Configuration page are
obtained by pressing page key 3 times to show - the
Configuration page, then press scroll key to get the configuration
parameter. The upper display indicates the parameter symbol, and
the lower display indicates the selected value of parameter.
There are two parameters which specity the data security function,
these are PASS ( password ) and CODE ( security code ).
Value of CODE
Value of PASS
Results
All parameters are changeable
0
1000
Any value
=1000
All parameters are changeable
Only Home page parameters are
changeable
All parameters are changeable
All parameters are not changeable
=CODE
=1000
=CODE
Others
Table 3.1 Password operation
3-2 Signal Input3-2 Signal Input
INPT:
Range:
UNIT:
Range:
DP:
Range:
INLO:
Selects the sensor type or signal type for signal input.
( thermocouple ) J_TC, K_TC, T_TC, E_TC, B_TC, R_TC
S_TC, N_TC, L_TC, C_TC, P_TC.
( RTD ) PT.DN, PT.JS
(linear ) 4-20, 0-20, 0-60, 0-1V, 0-5V, 1-5V, 0-10
Selects the process unit
C, F, PU( process unit ). If the unit is neither C nor F,
then selects PU.
Selects the resolution of process value.
( for T/C and RTD ) NO.DP, 1-DP
(for linear ) NO.DP, 1-DP, 2-DP, 3-DP
LL L L
Selects the low scale value for the linear type input.
INHI : Selects the high scale value for the linear type input.
INPT:
Range:
UNIT:
Range:
DP:
Range:
INLO:
INHI
:
UM0P411A
44