Setup
Enters the configuration page.
Select COMM for OUT4 or OUT5 . Set unequal addresses for those units
which are connected to the same port.
Set the Baud Rate ( ), and Parity Bit ( ) such that these values
are conform to PC setup conditions.
BAUD PARI
Enters the configuration page.
Select
COMM for OUT4 or OUT5 . Set unequal addresses for those units
which
are connected to the same port.
Set
the Baud Rate (),and Parity Bit ()such that these values
are
conform to PC setup conditions.
BAUD PARI
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable
should be modified for proper operation of RS-232 communication
according to Section 2-10.
If you use a conventional 9-pin RS-232 cable instead of CC94-1, the cable
should
be modified for proper operation of RS-232 communication
according
to
3 - 14 Retransmission3 - 14 Retransmission
The profiler can output (retransmit) process value or set point value
via its retransmission terminals RE+ and RE- provided that the
retransmission option is ordered. To accomplish this you can select
(REPV) or (RESP) for OUT4 or OUT5. The following
parameters should be configured for retransmission:
OP4L : Low limit value for output 4
OP4H : High limit value for output 4
REL4 : Retransmission low scale value for output 4
REH4 : Retransmission high scale value for output 4
OP5L : Low limit value for output 5
OP5H : High limit value for output 5
REL5 : Retransmission low scale value for output 5
REH5 : Retransmission high scale value for output 5
Example:
If you want to output 4 mA for PV at 0 C and 20mA for PV at
1000 C via output 5, then you should set the following
parameters:
L
L
OUT5 =
OP5L = 20.0 (%), since 20% of a 0-20mA output module
equipped will output 4 mA ( 20% of 20mA span ).
OP5H = 100.0 (%)
REL5 = 0 C
REH5 = 1000 C
L
L
UM0P411A
63