Table A.1 Error Codes and Corrective ActionsTable A.1 Error Codes and Corrective Actions
Error
Code
Display
Symbol
Error Description
Corrective Action
Illegal setup values been used:
Before COOL is used for OUT2,
DIRT ( cooling action ) has already
been used for OUT1, or PID mode
is not used for OUT1 ( that is PB
=0,and/orTI=0)
4
Communication error: bad function
code
10
Correct the communication
software to meet the protocol
requirements.
Communication error: register
address out of range
11
Don't issue an over-range
address to the slave.register
Communication error: attempt
to write a read-only data or a
protected data
14
Don't write a read-only data or a
protected data to the slave.
Communication error: write a
value which is out of range to a
register
15
Don't write an over-range data
to the slave register.
26
Fail to perform auto-tuning
function
EEPROM can't be written correctly
29
Return to factory for repair.
Return to factory for repair.
Input sensor break, or input
current below 1 mA if 4-20 mA is
selected, or input voltage below
0.25V if 1 - 5V is selected
39
Replace input sensor.
40
A to D converter or related
component(s) malfunction
Return to factory for repair.
Check and correct setup values of
OUT2, PB, TI and OUT1. IF OUT2
is required for cooling control, the
control should use PID mode ( PB
= 0, TI = 0 ) and OUT1 should
use reverse mode (heating action)
, otherwise, don't use OUT2 for
cooling control.
Check and correct setup values of
OUT2, PB, TI and OUT1. IF OUT2
is required for cooling control, the
control
should use PID mode ( PB
= 0, TI = 0 ) and OUT1 should
use reverse mode (heating action)
, otherwise, don't use OUT2 for
cooling control.
1.The PID values obtained after
auto-tuning procedure are out
of range. Retry auto-tuning.
1.The PID values obtained after
auto-tuning
procedure are out
of range. Retry auto-tuning.
2.Don't change set point value
during auto-tuning procedure.
2.Don't change set point value
during auto-tuning procedure.
3.Use manual tuning instead of
auto-tuning.
3.Use manual tuning instead of
auto-tuning.
5. Don't set a zero value for TI.5. Don't set a zero value for TI.
4. Don't set a zero value for PB.4. Don't set a zero value for PB.
6. Touch RESET key6. Touch RESET key
Cold junction compensation for
thermocouple malfunction
30
Return to factory for repair.Return to factory for repair.
Appendix A-1Appendix A-1
Holdback time out
25
You have selected an input type
which was not calibrated
Evaluate validity of the PID values
Calibrate the new input type or
change input type to the
calibrated one.
27
UM0P411D
97

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Brainchild P91 and is the answer not in the manual?

Brainchild P91 Specifications

General IconGeneral
BrandBrainchild
ModelP91
CategoryController
LanguageEnglish

Related product manuals