EasyManuals Logo

Brainchild P91 User Manual

Default Icon
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
The output 1 is used to drive the main heater, The output 2 is used to
drive the cooling fan, the output 3 is used for end of profile relay and the
output 4 is used to drive the auxiliary heater.
Temperature
Time
Figure 5.2 Temperature profile of the Heat Treatment OvenFigure 5.2 Temperature profile of the Heat Treatment Oven
The temperature profile is shown as Fig. 5.2. To achieve this profile,
the profiler is configured by the following setting:
400 CL
1000 CL
0
Global Data
Global Data
STAR = PV
END = OFF
DLAY = 0
PFR =CONT
HBT = 0.05
Profile Data
Profile Data
PROF = 1
HBBD = 50
RMPU = HH.MM
DLLU = HH.MM
SGNO = 1
SGTY = RAMP
TGSP = 400.0
RTRR = 25
P2EV = 0000
HBTY = 1
Segment Data
Segment Data
SGNO = 2
SGTY = DLL
P2EV = 0000
HBTY = 3
DLLT = 21
SGNO = 3
SGTY = RAMP
TGSP = 1000.0
RTRR = 9
P2EV = 1100
HBTY = 1
SGNO = 4
SGTY = DLL
P2EV = 1100
HBTY = 3
DLLT = 18
SGNO = 5
SGTY = RAMP
TGSP = 25.0
RTRR = 15
P2EV = 0001
HBTY = 2
SGNO = 6
SGTY = END
CYCL = 1
FSP = 25.0
Controller Configuration Data
Controller Configuration Data
ALF2 = ENDP
A2MD = 0000
INPT = K_TC
OUT1 = HTPC
O1FT = BPLS
UNIT = C
DP = 1_DP
CYC1 = 18.0
L
OUT2 = EVN1
OUT3 = ALM2
OUT4 = EVN3
OUT5 = REPV
OP5L = 0.0
OP5H = 100.0
REL5 = 0.0
REH5 = 1000.0
Auto-tuning is performed at 400 C for
PID1 and 1000 C for PID2.
L
L
Auto-tuning
UM0P411A
79
25 46 55 73 88

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Brainchild P91 and is the answer not in the manual?

Brainchild P91 Specifications

General IconGeneral
BrandBrainchild
ModelP91
CategoryController
LanguageEnglish

Related product manuals