2 HOLD : Applicable when unit is running
Event input close: Hold the profile
Event input open: Run profile again. Resume from the
segment where it hold earlier
3 ABOT: Applies when unit is in run mode
Requires only momentary type input
Event input close: Unit will abort the current running profile
and enter static mode.
4 MAN: Applies when unit is in static mode or run mode
Event input close: Outputs performs bumpless transfer
Event input open: Unit will perform normal PID operation
5 FTRA: Applies when unit is in static mode or run mode
Event input close: Performs failure transfer function
Event input open: Unit will perform normal PID operation
6 OFF: Applies when unit is in static mode or run mode
Event input close: All outputs/alarm turn off, profile stops
running
Event input open: If running, profile resumes where it was put
into off condition, outputs/alarms active again as per
configuration
7 PASS: Applies when unit is run mode
Requires only momentary type input to pass to next segment
Event input close: Profile will move ahead by 1 segment
8 PID2: Applies when unit is in static mode or run mode
UM0P411A
45-1
If chosen, close the event input pins the PB2, TI2 and TD2 will
replace PB1, TI1 and TD1 for control.