30
Installation and Operation Manual
X-DPT-Profibus-DP-Interface-eng
PN 541-C-068-AAG
November, 2008
For module 3:
The Mass Flow Meter is also making use of the special identifier byte after
which one of the two I/O configuration possibilities can be sent.
For module 1:
For module 2:
In case of a configuration tool, e.g. STEP7, see the example below.
Using STEP7, one can make a selection from one of the modules that are
declared in the GSD file. When selecting the slave type from the configuration
tool, see [1], this folder can be picked up and dragged into the PROFIBUS DP
master system rail [2]. The next step is to select one of the modules [1]. Here
the ‘maximum configuration’ is picked up and dragged into the slave module
slot [3]. Now the slave configuration is done and can be saved, compiled
downloaded into the S7 controller.
Byte Code Description
1 0xC1 Special identifier with one length byte each for Output and Input
follows, with one byte of vendor specific data
2 0x84 Output data, 5 bytes (1 float + 1 byte)
3 0x94 Input data, 21 bytes (4 floats + 1 unsigned integer + 1 byte)
4 0x03 Manufacturer specific data, module #3
Byte Code Description
1 0xC1 Special identifier with one length byte each for Output and Input
follows, with one byte of vendor specific data
2 0x80 Output data, 1 byte
3 0x8C Input data, 13 bytes (3 floats + 1 byte)
4 0x02 Manufacturer specific data, module #2
3
1
2
Byte Code Description
1 0x41 Special identifier with one byte length Input follows, with one byte of
vendor specific data
2 0x83 Input data, 4 bytes (1 float)
3 0x01 Manufacturer specific data, module #1