EasyManua.ls Logo

Brooks GF125 - Page 53

Default Icon
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operation Manual
X-DPT-EtherCAT-GF1XX-MFC-eng
Part Number: 541B219AAG
April, 2017
53
Section 5- Appendix
Brooks EtherCAT MFCs
0x600F:03 Ramp Active is set when the device is ramping from one
setpoint to another. The bit is cleared when the ramp is complete.
0xF383 bit 5 Active Device Error Details, Ramp Data is set when an invalid
Ramp Time is received. The bit is cleared when a valid ramp time is
received.
0xF383 bit 6 Active Device Error Details, Ramp Error is set when a Ramp
Time of zero is received by the device when a ramp is active.