3.3.3- Advanced Functions
3.3.3.1- Stop-start control
This mode enables you to keep the equipment on permanently, so that when the filtering pump starts
up, it will instruct the chlorinator to start-up. When the pump stops, the screen of the chlorinator will
display the message "stop".
To activate this mode, remove jumper "LK2" from the power board, supply the chlorinator directly at 230
V, and connect the "filter" inlets in parallel to the supply of the filtering pump. In this way, when the
filtration pump turns on, the “filter” input must be connected to 220V, and when the pump stops, “filter”
input connector must be at 0V.