6 – 14 Repair manual SWE100, 120, 120L, 120S, 140, 140L, 200D © BT
Functions and parameters
Parameters
T code Valid from serial no. Date Order no.
841×842×843 6061850- 2012-08-30 258946-120
104 Automatic log-
out, minutes
0/20 1 20 Determines the time until the truck is
switched off when the keypad is used.
Time is counted down from when the latest
power consumer is used. Value 0 gives 4
hours.
105 Collision
sensor, X level
0/100 1 0 Option. Indicates the degree of sensitivity
for what should be interpreted as a side
impact. Be sure to set this parameter when
installing the truck. For more information,
see the Installation chapter.
106 Collision
sensor, Y level
0/100 1 0 Option. Indicates the degree of sensitivity
for what should be interpreted as a frontal/
rear-end impact. Be sure to set this
parameter when installing the truck. For
more information, see the Installation
chapter.
107 Battery setting,
Ah
1/20 1 9 9 = Large battery
13 = Medium battery
17 = Small battery
For more information, see the text below
the table.
108 Calibrating 1 1 1 = Calibration of proportional valve.
Automatically reset to zero after completed
calibration. See the chapter on hydraulics
for complete instructions on how to
perform the calibration.
109 Battery charger,
battery type
0/3 1 0 Determines what type of battery will be
charged.
0 = No charging. Default setting. An error
code is displayed if this parameter has
been set to 0 when a battery charger has
been installed and factory parameter 1101
has been set to 1.
1 = Lead/acid battery
2 = Hawker Evolution battery. Size 134Ah,
174Ah, 201Ah.
3 = Exide gel-battery
For more information, see the Installation
chapter.
Param
eter
Designation/
unit
Min./
Max.
Incr
eme
nt
Def
ault
Description