EasyManua.ls Logo

Burkert 3280 - Led Display; Display Elements Standard; Display Elements NAMUR NE 107

Burkert 3280
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
Installation
Type 3280, 3285
7.5 LED display
With the aid of the positioner version and process controller version, it is possible to use the Bürkert-Communi-
cator Software to toggle the LED colors between standard and NAMUR NE 107.
7.5.1 Display elements standard
LED color Status Display
white continuously on Normal operation
yellow continuously on Valve completely open
flashing,
color alternates with
the colors of the valve
position
Out of specification: Ambient conditions or process
conditions for the device are outside the specified area.
Internal device diagnostics point to problems in the device
or the process properties
green continuously on Valve closed
red flashing,
color alternates with
the colors of the valve
position
Error
see chapter “9.3 Troubleshooting”, page 45
white, green or red flashing Is used to identify a device in the büS network. The
„flashing“ status is started in the Bürkert Communicator
Software when selecting the device
orange flashing,
color alternates with
the colors of the valve
position
Function check: Work is being carried out on the device;
controlled operation is therefore temporarily not possible
no color or LED off - Valve without power supply
7.5.2 Display elements NAMUR NE 107
LED color Color
code
Status Description Display
green 1 continu-
ously on
Diagnostics
active
Device is operating faultlessly. Status changes are shown
in color.
Messages are transmitted via any connected field bus.
red 5 continu-
ously on
Failure, error or
fault
Due to a malfunction in the device or on its periphery,
controlled operation is not possible.
green or
red
1 or 5 flashing Is used to identify a device in the büS network. The
„flashing“ status is started in the Bürkert Communicator
Software when selecting the device
orange 4 continu-
ously on
Function check The device is being worked on; controlled operation is
therefore temporarily not possible.
yellow 3 continu-
ously on
Outside the
specification
The ambient conditions or process conditions for the
device are outside the specified area.
Device internal diagnostics point to problems in the
device or with the process properties.
english