44
Start-up
Type 3280, 3285
8.3.3 Other settings
CAL INP
Calibration of the position set-point value (4...20 mA; 0...20 mA; 0...5 V; 0...10 V)
The set-point value input can be re-calibrated using this auxiliary function. Acceptance of the min. input signal
(0 mA; 4 mA; 0 V): Create the minimum value of the input signal at the input and confirm it in the software.
Acceptance of the max. input signal (20 mA; 5 V; 10 V): Create the maximum value of the input signal at the input
and confirm it in the software.
Calibration of the position actual value (4...20 mA; 0...20 mA; 0...5 V; 0...10 V)
This additional function can be used to recalibrate the actual input. Acceptance of the minimum input signal (0
mA; 4 mA; 0 V): Set the minimum value of the unit signal at the input and confirm value in the software. Accep-
tance of the maximum input signal (20 mA; 5 V; 10 V): Set the maximum value of the unit signal at the input and
confirm value in the software.
FACTORY RESET
Reset to the factory settings
Use this function to reset all user settings to the delivery status. All parameters, except for the calibration values,
are reset to default values. The hardware is subsequently reset.
DIAGNOSIS
Errors can be read via this function.
TOGGLE LED DISPLAY
Toggle the LED colors between standard and NAMUR NE 107
Use this function to toggle the colors for displaying the device status between standard and NAMUR NE 107.