37
Start-up
Type 3280, 3285
Parameterization
interface
büS or CANopen can be selected as a parameterization interface. See chapter
“7.3”
Communications
interface
In the case of the digital version, it is possible to communicate with the device via
büS/CANopen (e.g. set-point/actual values)
Functions for process controller only:
Function Description
Physical scaling of the
process variables
Function for scaling process actual value and process set-point value. See chapter
„8.3.2“
Process controller
optimization
Function for optimizing the process controller parameters. See chapter „8.3.2“
Process characteristic
linearization
Function for linearization of the process characteristics. See chapter „8.3.2“
Parameterization of the
PID process controller
Setting amplification factor (P-component), reset time (I-component), derivative
time (D-component), insensitivity range (dead band), filtering of the process actual
value input. See chapter „8.3.2“
Simulation of process
values
Simulation of actual values for testing device functions. See chapter „8.3.2“
Analog input (actual value
input)
4...20 mA; 0...20 mA; 0...5 V; 0...10 V can be set as standard signals. See chapter
„8.3.2“
In the case of the digital version, the actual value input can process not only the
standard signals but also frequency signals