29
EN
When2,3oramaximumof4ltersareoperated
in parallel, they must be electrically interlocked to
prevent simultaneous backwashing.
Insert an interlocking cable into the output of any
onelter,representinglter1,andrunthecableto
theinputoflter2.Insertthenextinterlockingcable
intotheoutputoflter2,andrunittotheinputof
lter3.Theoutputofthelastlterisreturnedtothe
inputoflter1.
The required backwash interval must be set at the
ltertobebackwashedrst(master)(seeabove).
Thesecondlter(slave)mustbesetasfollows:
Key Display
PressSetfor5seconds SL0
Displaydotsash
Device is in programming mode
PressSet SL1
Wait10seconds,dotsstopashing.
Thepressureappearsinthedisplay(0.0P,when
nowaterisused).
AthirdltermustbesettoSL2andafourthtoSL3.
Disconnectandreconnectalllterstothemains.
Thelterswillbebackwashedinsequence:Master,
SL 1, SL 2 and SL 3.
Thetimeuntilthenextbackwashingandthepres-
suredierenceappearalternatelyinthemasterlter
display.Thepressuredierenceisonlydisplayed
for large volumes of water.
Onlythepressuredierenceappearsintheslave
lterdisplay.
Theltersarereadyforuse.
Werecommendprogrammingtheltersothatthe
device is backwashed at least once a month to
preventforeignparticlesfromadheringtothelter
element(morefrequentlyforhigherlevelsofsoiling;
factorysettingevery7days).
Should the local water quality (degree of contami-
nation)change,thebackwashingintervalmustbe
corrected;seecommissioning.
Unplugging and plugging in the device can back-
wash it at any time.
Thetimeuntilthenextbackwashingandthepres-
sure dierence appear alternately in the display.
Thepressuredierenceisonlydisplayedforlarge
volumes of water.
Clean plastic parts with a soft, damp cloth only;
do not use solvents, detergents, or acidic cleaning
agents.