ENABLE/DISABLE RELAYS
This function allows the disablement of one or more of the panel’s 3 auxiliary relays from activating as
programmed.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Relays.
When selected, press Accept
4button and windows similar to the ones below will appear:
Select the relay (1, 2 or 3) to be disabled/enabled using the
5and 6 scroll buttons.
When the desired output set has been selected, press the Accept
4button and the relay’s status
(Enabled or Disabled) will flash. Next, press the
5and6 scroll buttons to toggle between enabled
and disabled and press the Accept
4button to select. The window will now move to the next relay
allowing further enablements or disablements to be made. Alternatively, to return to the previous
menu press the Escape
3button.
Panel Relay : 1
Panel Relay : 1
Enabled
ENABLE/DISABLE OUTPUTS
This function allows you to disable one or more output sets from activating in a fire condition. It is
typically used to disable, for example, auto-diallers to monitoring stations, roller shutter doors, etc.
from activating during routine maintenance.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Outputs.
When selected, press the Accept
4button and windows similar to the ones below will appear:
Select the output set (1 to 16 or ALL) to be disabled/enabled using the
5and6 scroll buttons.
When the desired output set has been selected, press the Accept
4button and the output set’s status
(Enabled or Disabled) will flash. Next, press the
5and6 scroll buttons to toggle between enabled
and disabled and press the Accept
4button to select. The window will now move to the next output
set allowing further enablements or disablements to be made. Alternatively, to return to the previous
menu press the Escape
3button.
Output Set: All Output Set: All
Enabled
ENABLE/DISABLE SOUNDERS
Note: The disablement of individual sounder groups is non-compliant with EN54-2.
Note: Changes made to the CONFIGURE SOUNDER DISABLEMENTS function, see page 32, will have an
affect on the options available at this menu.
This function allows you to disable one or more sounder groups from sounding in a fire condition.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Sounders.
When selected, press the Accept
4button and windows similar to the ones below will appear:
Select the sounder group (1 to 16 or ALL) to be disabled/enabled using the
5and6 scroll buttons.
When the desired sounder group has been selected, press the Accept
4button and the sounder
group’s status (Enabled or Disabled) will flash. Next, press the
5and6 scroll buttons to toggle
between enabled and disabled and press the Accept
4button to select. The window will now move to
the next sounder group allowing further enablements or disablements to be made. Alternatively, to
return to the previous menu press the Escape
3button.
Sounder Group: All Sounder Group: All
Enabled
CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 35 of 48