For the high pressure single and dual-pump motors of 30RB/RBP 170R-950R units (options 116R, 116S, 116V, 116W)
No.
(2)
Description
(3)
170R 190R 210R 230R 270R 310R 340R 380R 410R 450R
1 Nominal eciency at full load and nominal voltage % 87,5 87,5 87,5 87,5 89,6 89,6 89,7 89,7 89,7 90,8
1 Nominal eciency at 75% of full load and nominal voltage % 88,2 88,2 88,2 88,2 90,4 90,4 90 90 90 90,8
1 Nominal eciency at 50% of full load and nominal voltage % 87,5 87,5 87,5 87,5 89,9 89,9 89 89 89 89,6
2 Eciency level - IE3
3 Year of manufacture -
This information varies depending on the manufacturer and
model at the time of incorporation. Please refer to the motor
name plates,
4
Manufacturer's name and trademark, commercial registration
number and head oce of manufacturer
- Same as above
5 Product model number - Same as above
6 Number of motor poles - 2
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 3 3 3 3 4 4 5,5 5,5 5,5 7,5
7-2 Maximum input power (400 V)
(4)
kW 3,44 3,44 3,44 3,44 4,49 4,49 6,17 6,17 6,17 8,32
8 Nominal input frequency Hz 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)
(5)
A 6,33 6,33 6,33 6,33 7,75 7,75 10,40 10,40 10,40 14,10
10 Nominal speed
r/s -
rpm
48 - 2900
11 Product disassembly, recycling or disposal at end of life -
Disassembly using standard tools. Disposal and recycling using
an appropriate company
12
Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C
Please refer to the operating conditions given in this manual or
in the specic conditions given in the selection programs.
IV - Potentially explosive atmospheres - Non ATEX environment
No.
(2)
Description
(3)
480R 550R 610R 670R 720R 770R 820R 870R 950R
1 Nominal eciency at full load and nominal voltage % 90,8 90,8 91,6 91,6 91,6 93,1 93,1 93,1 93,1
1 Nominal eciency at 75% of full load and nominal voltage % 90,8 90,8 92,2 92,2 92,2 93,3 93,3 93,3 93,3
1 Nominal eciency at 50% of full load and nominal voltage % 89,6 89,6 91,7 91,7 91,7 92,7 92,7 92,7 92,7
2 Eciency level - IE3
3 Year of manufacture -
This information varies depending on the manufacturer and
model at the time of incorporation. Please refer to the motor
name plates,
4
Manufacturer's name and trademark, commercial registration number
and head oce of manufacturer
- Same as above
5 Product model number - Same as above
6 Number of motor poles - 2
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 7,5 7,5 11 11 11 15 15 15 15
7-2 Maximum input power (400 V)
(4)
kW 8,32 8,32 12,00 12,00 12,00 16,20 16,20 16,20 16,20
8 Nominal input frequency Hz 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)
(5)
A 14,10 14,10 20,20 20,20 20,20 26,60 26,60 26,60 26,60
10 Nominal speed
r/s -
rpm
48 - 2900
11 Product disassembly, recycling or disposal at end of life -
Disassembly using standard tools. Disposal and recycling using
an appropriate company
12
Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C
Please refer to the operating conditions given in this manual or
in the specic conditions given in the selection programs.
IV - Potentially explosive atmospheres - Non ATEX environment
(1) Required by regulation No. 2019/1781 concerning the application of directive 2009/125/EC on the ecodesign requirements for electric motors.
(2) Item number imposed by regulation No. 2019/1781, annex I2b.
(3) Description given by regulation No. 2019/1781, annex I2b.
(4) To obtain the maximum input power for a unit with a hydraulic module, add the “maximum operating input power” for the unit (see Electrical data table) to the
pump power.
(5) To obtain the maximum operating intensity for a unit with a hydraulic module, add the “maximum operating intensity” for the unit (see Electrical data table) to the
pump intensity.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS