Options No. Description Advantages
30RB/RBP 
170-950
30RQ/RQP 
165-520
Welded connection 
sleeve for 
desuperheater
304 DSH inlet/outlet welded connection sleeves Easy installation 170-950 165-520
Free cooling (total) 305A
Free cooling hydraulic coils on the two 
refrigerant circuits
Energy savings for applications which 
require cooling all year round (e.g.: industrial 
processes, data centres)
170-950 No
Free cooling (partial) 305B
Free cooling hydraulic coils on a refrigerant 
circuit
Energy savings for applications with reduced 
demand for cooling in the winter (e.g. oce 
space with computer room, meeting rooms) 
170-950 No
Water buer tank 
module
307 Built-in water buer tank module
Avoids short cycle on compressors and 
ensures stable water in the loop
170-950 165-520
Free cooling mode 
drycooler 
management 
313
Control & connections to a Free Cooling 
Drycooler 09PE or 09VE tted with option 
FC control box
Easy system management, control 
capabilities extended to a drycooler used in 
Free Cooling mode
170-950 165-520
Compliance with  
UAE regulations
318
Additional label on the unit with input 
power, current and EER under rated 
conditions in accordance with  
AHRI 550/590
Compliance with ESMA standard  
UAE 5010-5:2019.
170-950 No
Compliance with 
Qatar regulations
319
Specic name plate on the unit with 415 V 
+/-6% power supply
Compliance with KAHRAMAA regulations  
in Qatar
170-950 No
Installation or 
application process 
outside Europe 
326
Specic management of option 
compatibility
Permits non-standard option compatibility  
for HVAC application in the EU
30RB 
170R-380R 
30RBP 
170R-950R
No
Compliance with 
Moroccan regulations
327 Specic regulatory documentation Compliance with Moroccan regulations 170-950 165-520
Plastic cover 331
Unit wrapped in a plastic cover and 
strapped onto a wooden pallet.
Protects against dust and external soiling of 
the unit during storage and transport.
170-950 165-520
12.2 - Description
12.2.1 - Hydraulic module without variable speed 
(Options 116R, 116S, 116T, 116U)
The hydraulic module is composed of the system's main hydraulic 
components:  factory-tted  water  pump,  screen  lter  and  relief 
valve. 
The xed-speed operating pressure pump provides the nominal 
ow rate for the system water loop.
Several types of water pump are available to suit all applications: 
 - Single or dual low pressure pumps 
 - Single or dual high pressure pumps. 
The nominal ow rate of the system should be adjusted using a 
manual control valve provided by the customer. 
The relief valve placed on the water inlet pipes at the pump inlet 
limits the pressure to 400 kPa (4 bar).
A screen lter that can be easily removed is placed at the pump 
inlet and protects the pump and the plate heat exchanger against 
solid particles that are greater than 1.2 mm.
Additional options can be ordered if necessary:
 - Option 42A (42B if option 307): hydraulic module protection 
(42A) or hydraulic module and buer tank protection (42B) 
down to an outdoor temperature of -20 °C.
 - Option 293: Expansion tank for water circulation system.
IMPORTANT: The use of the hydraulic module on open 
systems is prohibited.
12.2.2 - Hydraulic module with variable speed 
(Options 116V, 116W)
The composition of the hydraulic module with variable speed is 
similar to that of the hydraulic module without variable speed.
In this case, the pump is controlled by a variable frequency drive 
that allows the pump's nominal ow rate to be adjusted according 
to the chosen  control  mode  (constant  pressure  or temperature 
differential,  or  fixed  speed)  and  the  installation  operating 
conditions.
IMPORTANT: The use of the hydraulic module on open systems 
is prohibited.
12 - OPTIONS 