Procedure for controlling the pressure dierential setpoint
Once the circuit is cleaned, place the hydraulic circuit in the 
conguration for which the unit selection was performed (generally, 
this will be all valves open and all cooling coils active)
Read the ow rate on the user interface and compare the value 
obtained with the theoretical value of the selection:
 - If the ow rate read is greater than the preset value, reduce 
the  pressure  dierential  setpoint  on  the  user  interface  to 
reduce the ow rate value;
 - If the ow rate read is lower than the preset value, increase 
the  pressure  dierential  setpoint  on  the  user  interface  to 
increase the ow rate value
Repeat until the unit's nominal ow rate at the required operation 
point is achieved.
Stop the forced operation of the pump and proceed to the 
conguration of the unit for the required control mode. Modify the 
control parameters:
 - Set water ow rate control to “pressure dierential”
 - Set the value of the required pressure dierential.
The  unit's  default  factory  conguration  is  the  minimum  speed 
(frequency: 30 Hz).
NOTE:
If  during  adjustment,  the  low  or  high  frequency  limits  are 
reached  before  reaching  the  specied  ow  rate,  keep  the 
pressure dierential value at its lower or higher limit as the 
control parameter value.
If the user knows in advance the pressure dierential value 
at the unit outlet to be maintained, this value can be entered 
directly  as  a  parameter  to  be  declared.  You  should  not, 
however, omit the hydraulic circuit cleaning sequence
9.4 - Units with hydraulic module and variable-
speed pump – Temperature dierential control
The installation ow rate has not been set to a rated value.
The  ow  rate  will  be  adjusted,  by  varying  the  pump  speed, 
 
to maintain a heat exchanger temperature dierential value dened 
by the user. 
This is checked by the temperature sensors at the water exchanger 
inlet  and  outlet  (items  8  and  9  on  the  typical  hydraulic  circuit 
diagram).
The system reads the measured temperature values, calculates 
the corresponding Delta T°, compares it with the setpoint value 
set by the user and then modulates the pump speed accordingly.
 - This  results  in  an  increase  in  the  ow  rate  if  the  Delta  T 
exceeds the setpoint.
 - This results in a decrease in the ow rate if the Delta T is less 
than the setpoint. 
This variation in ow rate is limited by the maximum and minimum 
permissible ow rate values for the unit and by the maximum and 
minimum pump supply frequency values.
The  maintained  Delta  T  may,  in  certain  cases,  dier  from  the 
setpoint value:
 - If the setpoint value is too high (corresponding to a ow rate 
lower than the minimum value or a frequency less than the 
minimum value), the system will be limited to the minimum 
flow rate or minimum frequency, which will result in a 
 
Delta T below the setpoint,
 - If the setpoint value is too low (corresponding to a ow rate 
higher than the maximum value or a frequency greater than 
the  maximum  value),  the  system  will  be  limited  to  the 
maximum ow rate or maximum frequency, which will result 
in a Delta T above the setpoint. 
Contact the manufacturer's Service to implement the procedures 
described below.
Hydraulic circuit cleaning procedure
Refer to the hydraulic circuit cleaning procedure.
Procedure for adjusting the Delta T setpoint
Once the circuit is cleaned, stop the forced operation of the pump 
and proceed to the conguration of the unit for the required control 
mode.
Modify the control parameters:
 - Water ow rate control method (temperature dierential)
 - Set the required Delta T.
The  unit's  default  factory  conguration  is  the  minimum  speed 
(frequency: 30 Hz).
9.5 - Units with hydraulic module and variable-
speed pump - Setting a xed ow rate for the 
system
The ow  will  be  set  to  a  nominal  value. This value will remain 
constant, and will not be dependent on variations in the 
installation's load.
Contact the manufacturer's service department to implement the 
procedures described below
Hydraulic circuit cleaning procedure
Refer to the hydraulic circuit cleaning procedure.
Procedure for controlling the ow rate
Once the circuit has been  cleaned, set the required water ow 
rate by adjusting the pump frequency on the user interface.
Stop the forced operation of the pump and proceed to the 
conguration of the unit for the required control mode. Modify the 
control parameters:
 - Water ow rate control method (xed speed)
 - Constant frequency value.
The  unit's  default  factory  conguration  is  the  minimum  speed 
(frequency: 30 Hz).
9 - NOMINAL SYSTEM WATER FLOW RATE CONTROL