4.3 - Free spaces
The free spaces presented are determined in order to ensure 
sucient working and manoeuvring space to carry out maintenance 
operations on the unit in suitable ergonomic conditions
Key:
All dimensions are given in mm.
B
Clearances required for maintenance and air ow
C
Clearance recommended for coil removal
4.4 - Positioning of potentially ammable zones 
around the unit
Electrical cabinet side
The complete unit, including all the options and accessories which 
are provided by the manufacturer, have been certied for use with 
an A2L refrigerant.
To ensure this, the manufacturer complies with EN 378-2 §6.2.14 and 
has dened  a potentially ammable  zone using EN  60079-10-1 in 
order to identify where no sources of ignition must be present. 
 
The manufacturer has then designed the machine so that, if the unit 
is used in the manner for which it has been designed, there are no 
internal sources of ignition in the potentially ammable zone inside 
the machine. 
Therefore, the only residual risk is that a source of ignition is 
introduced into the potentially ammable zone by the user. This 
is why the manufacturer has decided to show the potentially 
ammable zone around the machine (see the diagram above) into 
which the user must not introduce any sources of ignition.
This indication is only provided to help our customers to identify 
the limits of the ammability risk.
However, the machine itself does not present any risk of explosion 
connected to the use of A2L refrigerant.
Note (the following information is provided by the manufacturer 
for information purposes only. The application of the following 
directives is the sole responsibility of the user):
In compliance with the directives 2009/104/EC and 1999/92/EC, 
these zones may be qualied as ATEX zones by the user on the 
basis of their own risk analysis, for which they alone remain 
responsible. In accordance with the denition given by Annex I of 
the directive 1999/92/EC, this zone may be classied as zone 2 
since it may consist of a location where an explosive atmosphere 
consisting of  a mixture  of air and  ammable substances  in the 
form of a gas is not liable to occur during normal operation or, 
 
if it does occur, it only occurs for a short period of time.
If additional equipment is required (motorised valve, pump, etc.), 
it must be: 
 - Installed outside of the dened potentially ammable zone 
 - Certied as not being a source of ignition for the refrigerant 
used.
4.5 - Installing several units 
It is recommended to install multiple units in a single row, arranged 
as shown in the example below, to avoid recycling air between 
the units. If the oor space does not allow this arrangement, contact 
your distributor to assess the various installation options.
1500 mm min.
1500 mm
min.
4.6 - Distance to the wall
Plots
Antivibratiles
S
H
h
To guarantee correct operation in most cases:
If h < H, S minimum = 3 m
If h > H or S < 3 m, contact your distributor to assess the various 
installation options.
4 - DIMENSIONS, CLEARANCES, MINIMUM INSTALLATION DISTANCES
9
Anti-vibration 
mountings