EasyManua.ls Logo

Carrier 30RBP-170R - NOMINAL SYSTEM WATER FLOW RATE CONTROL

Carrier 30RBP-170R
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 - NOMINAL SYSTEM WATER FLOW RATE CONTROL
Refer to the schematic diagram in the “Hydraulic connections”
paragraph for all item references in this chapter.
The water circulation pumps of the units in the range have been
designed to allow the hydraulic modules to operate in all possible
congurations  depending  on  the  specic  system  conditions, 
i.e. with water inlet/outlet temperature di󰀨erences (Delta T) at full 
load which vary from 3 to 10 K.
This temperature di󰀨erence required between the water inlet and 
outlet determines the nominal ow  rate of  the system. Use the 
specication provided  when selecting  the unit  to determine  the 
system's operating conditions.
In particular, collect the data to be used for the control of the system
ow rate:
- For a unit without hydraulic module: nominal pressure drop
at the unit terminals (plate heat exchanger + internal pipe). 
This is measured with pressure gauges that must be installed
at the inlet and outlet of the unit (item 21).
- Units with fixed-speed pumps: nominal flow rate.
The pressure of the uid is measured by sensors installed at 
the inlet of the pump and outlet of the unit (items 7 and 10). 
The  system  calculates  the  ow  rate  associated  with  this 
di󰀨erential pressure. The ow rate can be read directly on 
the user interface (refer to the control manual for the range).
- Units with variable-speed pumps – control on pressure
di󰀨erential:  pressure  di󰀨erential  at  the  hydraulic  module 
terminals,
- Units with variable-speed pumps – control on temperature
di󰀨erential: nominal temperature di󰀨erence at the exchanger.
If this information is not available when the system is commissioned,
contact the engineering and design department responsible for
the system to obtain it.
This data can be obtained either from the performance tables
included in the technical documentation (for cases where the water 
type  heat  exchanger  temperature  delta  is  5  K)  or  from  the 
“Electronic Catalogue” selection program for all other applicable 
temperature delta in the range of 3 to 10 K.
9.1 - Units without hydraulic module
General information
The nominal ow rate of the system will be set using a manual 
valve that should be installed on the water outlet pipe (item 22 on 
the typical hydraulic circuit diagram).
Due to the pressure drop it generates on the hydraulic system,
this ow rate control valve is used to set the system pressure/ow 
rate  curve  to  the  pump  pressure/ow  rate  curve,  to  obtain  the 
nominal ow rate at the desired operation point.
This is checked by reading the pressure drop on the unit
(plate heat exchanger + internal piping).
As the exact total system pressure drop is not known upon
commissioning, it is necessary to adjust the water ow rate with 
the control valve to obtain the installation's specic ow rate.
Hydraulic circuit cleaning procedure
- Open all control valves completely (item 22).
- Start up the system pump.
- Read the pressure drop as the di󰀨erence between the unit inlet
and outlet pressures on the pressure gauge (item 21).
- Let  the  pump  run  for  2  hours  continuously  to  ush  the 
system's hydraulic circuit (presence of contaminating solids).
- Perform another reading.
- Compare this value to the initial value.
- A changed value indicates that the lters in the system need 
to be removed and cleaned. In this case, close the shut-o󰀨
valves on the water inlet and outlet (item 19) and remove the 
lters then clean (items 1 and 20) after draining the hydraulic 
part of the unit (items 6).
- Remove the air from the circuit (items 5 and 17).
- Repeat until all fouling is removed from the lter.
Water ow rate adjustment procedure
Once the circuit has been decontaminated, read the pressures on
the  pressure  gauges  (water  inlet  pressure  -  outlet  pressure) 
to determine the pressure drop across the unit terminals
(plate heat exchanger + internal piping).
Compare the value obtained to the theoretic value of the selection
(WARNING: Take into account the pressure drop on the lter if it 
is located between the pressure gauges).
If  the  pressure  drop  reading  is  above  the  specied  value,  this 
indicates that the ow rate at the terminals of the unit (and therefore
within the system) is too high. In this case, close the control valve 
and read the new di󰀨erence in pressure.
Repeat  by  successively  closing  the  control  valve  (item  22) 
until  the  nominal  ow  rate  is  achieved  at  the  unit's  required 
operation point
NOTE:
If the system has an excessive pressure drop in relation to
the available static pressure delivered by the system's pump,
the nominal water flow rate cannot be obtained (lower
resulting ow rate) and the temperature di󰀨erence between
the water inlet and outlet of the water type heat exchanger
will be increased.
To reduce the installation's hydraulic system pressure drop, it is
necessary to:
- Reduce the pressure drops of individual components (bends, 
level changes, options, etc.) as much as possible;
- Use the correct pipe diameter;
- Avoid extending the hydraulic systems when possible.
9.2 - Units with hydraulic module and
xed-speed pump
General information
See the paragraph on “Units without hydraulic module”
Hydraulic circuit cleaning procedure
- Open all control valves completely (item 22).
- Start up the unit's pump.
- Read the ow rate on the user interface.
- Let  the  pump  run  for  2  hours  continuously  to  ush  the 
system's hydraulic circuit (presence of contaminating solids).
- Perform another reading.
- Compare this value to the initial value.
- Adecrease in the ow rate value indicates that the lters in 
the system need to be removed and cleaned. In this case,
close the shut-o󰀨 valves on the water inlet and outlet (item 19) 
and  remove  the  lters  (items  20  and  1)  after  draining  the 
hydraulic part of the unit (items 6).
- Remove the air from the circuit (items 5 and 17).
- Repeat until all fouling is removed from the lter
39

Table of Contents

Related product manuals