Combination of options for the periods when the unit is in 
standby mode.
Ambient unit 
temperature range
30RB/RBP 170-950 or 30RQ/RQP 165-520
without option 116 with option 116
> 0 °C to 51 °C - -
-20 °C to 0 °C
Option 41
or
Suitable antifreeze 
solution  
(glycol, for example) 
Option 42A/B
(1)
 
or
Suitable antifreeze 
solution  
(such as glycol)
(1)
(1)  Allow the pumps to circulate. If there is a valve, install a bypass (see diagram 
for winter position).
If the system is isolated by a valve, it is imperative to install a 
bypass as indicated below.
Winter position
Unit
Water network
Closed
Closed
Open
IMPORTANT REMINDERS:
Depending on the atmospheric conditions in your region, 
 
you need to:
 - Add an appropriate antifreeze solution agreed by the 
manufacturer (maximum of 45%) to protect the system 
down  to  a  temperature  of  10  K  below  the  lowest 
temperature likely to occur locally.
 - For extended shut-downs, drain and add an anti-freeze 
solution  to  the  heat  exchanger  (use  the  drain  valve 
located at the water inlet).
 - To prevent corrosion due to dierential aeration, if the 
system is to be empty for more than 1 month, the heat 
transfer uid circuit should be protected with a blanket 
of  neutral  gas  (0.5  bar  maximum).  If  the  heat  transfer 
uid does not meet the manufacturer's recommendations, 
a nitrogen blanket must be applied immediately.
 - In case of prolonged non-usage, the hydraulic circuits 
must be protected by circulating a passivating solution 
(consult a specialist).
 - At the start of the next season, rell the unit with water 
and add an inhibitor.
 - If  auxiliary  equipment  is  installed  in  the  system,  the 
installer  must  ensure  that  the  resultant  ow  rates are 
still within the minimum and maximum values indicated 
in the operating limits table (application data).
 - If frost protection is dependent on electric heaters, never 
de-energize the unit when frost protection is required. 
To ensure protection, the main unit disconnect switch 
and the auxiliary heater protection circuit breaker must 
be  closed  (see  wiring  diagram  to  locate  these 
components). If it is not to be used in freezing conditions, 
or  during  a  prolonged  power  failure  (planned  or 
unplanned), the water type heat exchanger and external 
pipes must be drained without delay. Damage caused by 
frost is not covered by the warranty.
 - The heat exchanger temperature sensors are an essential 
frost protection element: if piping trace heaters are used, 
ensure  the  external  heaters  do  not  affect  the 
measurements provided by these sensors. 
 - If  there  is  a  Water  Type  Heat  Exchanger  Connection 
sleeves option, it is necessary to install a heater on each 
extension in order to protect the water pipes down to an 
outdoor temperature of 0 °C. The anti-freeze and heater 
solutions can be combined.