EasyManua.ls Logo

Carrier 30RBP-170R - Page 56

Carrier 30RBP-170R
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.2.3 - Partial heat recovery (Option 49)
This option enables free hot water to be produced using heat recovery by desuperheating the compressor discharge gases. The option
is available for the entire RB/RBP and RQ/RQP range.
A plate heat exchanger is installed in series with the air-cooled exchanger coils on the compressor discharge line of each circuit.
The control conguration for the desuperheater option is factory-assembled (see chapter 12.2.3.4 - Operation). The installer must 
protect the heat exchanger against frost.
12.2.3.1 - Physical properties of units with partial heat recovery using desuperheaters
30RB/RBP 170R 190R 210R 230R 270R 310R 340R 380R 410R 450R
Desuperheater in circuits A/B Brazed-plate heat exchanger
Water volume circuits A/B l
2 /
3,75
2 /
3,75
3,75 /
3,75
3,75 /
3,75
3,75 /
3,75
3,75 /
5,5
3,75 /
5,5
5,5 /
5,5
5,5 /
5,5
5,5 /
7,5
Maximum operating pressure, water side kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic connections Victaulic
Connection in 2" 2" 2" 2" 2" 2" 2" 2" 2" 2"
External diameter mm 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3
30RB
Operating weight
(1)
Standard unit + desuperheater option kg 1409 1457 1457 1581 1616 2055 2109 2271 - -
Unit with option 15LS + desuperheater option
(2)
kg 1492 1540 1540 1690 1725 2182 2236 2416 - -
Unit with option 15LS + option 116W + desuperheater option
(2)
kg 1627 1675 1675 1825 1871 2331 2431 2611 - -
Unit + option 15LS + option 116W + option 307 +
desuperheater option
(2)
kg 2610 2658 2658 2808 2854 3318 3417 3597 - -
30RBP
Operating weight
(1)
Standard unit + desuperheater option kg 1409 1457 1457 1581 1616 2055 2109 2271 2329 2757
Unit with option 15LS + desuperheater option
(2)
kg 1492 1540 1540 1690 1725 2182 2236 2416 2474 2920
Unit with option 15LS + option 116W + desuperheater option
(2)
kg 1627 1675 1675 1825 1871 2331 2431 2611 2669 3154
Unit + option 15LS + option 116W + option 307 +
desuperheater option
(2)
kg 2610 2658 2658 2808 2854 3318 3417 3597 3654 4146
30RB/RBP 480R 550R 610R 670R 720R 770R 800R 870R 950R
Desuperheater in circuits A/B Brazed-plate heat exchanger
Water volume circuits A/B l
5,5 /
7,5
7,5 /
7,5
7,5 / 11 11 / 11 11 / 11 11 / 15 11 / 15 15 / 15 15 / 15
Maximum operating pressure, water side kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic connections Victaulic
Connection in 2" 2" 2" 2" 2" 2" 2" 2" 2"
External diameter mm 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3
30RB
Operating weight
(1)
Standard unit + desuperheater option kg - - - - - - - - -
Unit with option 15LS + desuperheater option
(2)
kg - - - - - - - - -
Unit with option 15LS + option 116W + desuperheater option
(2)
kg - - - - - - - - -
Unit + option 15LS + option 116W + option 307 +
desuperheater option
(2)
kg - - - - - - - - -
30RBP
Operating weight
(1)
Standard unit + desuperheater option kg 2782 2987 3325 3571 3571 4102 4102 4351 4351
Unit with option 15LS + desuperheater option
(2)
kg 2945 3168 3458 3724 3724 4276 4276 4545 4545
Unit with option 15LS + option 116W + desuperheater option
(2)
kg 3179 3439 3768 4034 4034 4665 4665 4934 4934
Unit + option 15LS + option 116W + option 307 +
desuperheater option
(2)
kg 4171 4431 4775 5041 5041 5686 5686 5955 5955
(1)  Weights are guidelines only. Refer to the unit name plate.
(2)  Options: 15LS = Very low noise level, 116W = Variable-speed high pressure dual-pump hydraulic module, 307 = Water bu󰀨er tank module,
12 - OPTIONS
56

Table of Contents

Related product manuals