Figure 1: Water connections without hydraulic
module
Figure 2: Hydraulic connections with
hydraulic module
Example: Single-pump
Coupling for expansion
vessel (option 293)
Presence of a
stainless steel lter
Example: Dual-pump
Coupling for expansion
vessel (option 293)
Presence of a
stainless steel lter
Figure 3: Hydraulic connections with hydraulic
module and with bu󰀨er tank module option
A
15
5
23
6
Key
Components of the hydraulic module and the unit
1  Screen lter (particle size of 1.2 mm)
2  Expansion tank (option)
3 Relief valve
4  Circulating pump (single or dual)
5 Air vent
6 Water drain tap
7 Pressure sensor
Note: Provides pressure information for the pump inlet (see Control manual)
8 Temperature sensor
Note: Provides temperature information for the water exchanger outlet
(see Control manual)
9 Temperature sensor
Note: Provides temperature information for the water type heat exchanger inlet
(see Control manual)
10 Pressure sensor
Note: Provides pressure information for the water exchanger outlet (see Control 
manual)
11  Check valve (If dual-pump)
12 Plate heat exchanger
13  Heater or heat trace cable for frost protection (Option)
14  Water type heat exchanger ow rate sensor 
15  Water bu󰀨er tank module (Option)
Installation components
16 Pocket
17 Air vent
18 Flexible connection
19  Shut-o󰀨 valve
20  800 µm screen lter (mandatory for a unit without a hydraulic module)
21 Pressure gauge
22  Water ow control valve
Note: not required if hydraulic module with variable-speed pump
23 Charging valve
24  Bypass valve for frost protection (if shut-o󰀨 valves are closed (item 19) during 
winter)
25  Bu󰀨er tank (if required)
----  Hydraulic module (unit with hydraulic module option)
Notes:
- The installation must be protected against freezing.
- The unit's hydraulic module and the water type heat exchanger may be protected
(factory-tted  option)  against  freezing  using  electric  heaters  and  heat  trace 
cables (13)
- The pressure sensors are assembled on connections without Schrader.
Depressurise and drain the system before any work.
8 - WATER CONNECTIONS