12.2.6 - Brine option (Option 6B)
Brine production from 5 °C to -8 °C is only possible with the
low-temperature brine solution option (6B).
The unit is equipped with insulation on the intake tubes.
The insulation is reinforced on the low-temperature brine solution
option.
The operating range is based on:
- The size of the machine,
- The type of glycol,
- Its concentration,
- The ow rate,
- The temperature of the glycol solution,
- The condensing pressure (ambient temperature).
Operating range
- Low water temperature brine solution (ethylene glycol or propylene glycol)
Operating range Standard unit
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-10-9-8-7-6-5-4-3-2-10 123456789101112131415161718192021
48
52
30RBP
only
Brine option 6B
Part load
Part load
30RBP 610R-950R only
Inlet air temperature (°C)
Water outlet temperature (°C)
Operating range Unit option 15LS
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-10-9-8-7-6-5-4-3-2-10 123456789101112131415161718192021
48
44
30RBP
only
Brine option 6B
Part load
Part load
RB-RBP 610R-950R
Inlet air temperature (°C)
Water outlet temperature (°C)
1.  Water type heat exchanger ∆T = 5K.
2.  The hydraulic and/or water type heat exchanger module must be must be protected against frost (option 41 or 42A or 42B) or the
loop must be protected by an antifreeze solution for outdoor temperatures < 0 °C.
3. These ranges are guidelines only. Verify the operating range with the electronic catalogue.
Key
Operating range at full load
Extension of the operating range, 30RBP unit: Frost protection required (see note 2).
Operating range of units at part load
Extension of the operating range, unit with option 6B
Refrigerant charge for the low-temperature brine solution option
30RB/RBP 170R 190R 210R 230R 270R 310R 340R 380R 410R 450R
Refrigerant
(1)
Circuit A
kg 4,9 7,4 7,4 8,6 8,6 10,8 11,5 15,6 16,2 16,5
tCO
2
e 3,3 5,0 5,0 5,8 5,8 7,3 7,8 10,5 10,9 11,1
Circuit B
kg 8,6 8,6 8,6 8,6 8,6 15,1 15,8 15,6 16,2 19,7
tCO
2
e 5,8 5,8 5,8 5,8 5,8 10,2 10,7 10,5 10,9 13,3
30RB/RBP 480R 550R 610R 670R 720R 770R 800R 870R 950R
Refrigerant
(1)
Circuit A
kg 30,2 20,5 19,7 20,9 20,9 22,5 22,5 26,6 26,6
tCO
2
e 20,4 13,8 13,3 14,1 14,1 15,2 15,2 18,0 18,0
Circuit B
kg 32,4 20,5 20,9 20,9 20,9 26,6 26,6 26,6 26,6
tCO
2
e 21,9 13,8 14,1 14,1 14,1 18,0 18,0 18,0 18,0
(1)  For a combination of option 50 and 6B, refer to the unit name plate.
12 - OPTIONS
69