12.2.7 - Units with fans with available pressure
(Option 12)
The design of this range using R32, is intended for outdoor
installation. More more details on the various installation scenarios,
refer to the installation guide for A2L refrigerants. Units with fans
with available pressure are designed to be ducted to the fan
discharge which results in pressure drops in the air circuit.
It is for this reason that more powerful fan motors are installed for
this option.
For each installation, the duct pressure drops dier, depending
on the duct length, the duct section and the changes in direction.
Ductable units equipped with this option are designed to operate
with ducts whose air evacuation generates a maximum pressure
drop of 200 Pa.
Using a speed variation up to 19 rps enables the system to
overcome the pressure drops in the ducts while maintaining an
optimised air ow in each circuit.
All the fans in the same circuit run at the same time at the same
speed.
In the cooling/heating mode, the full load or part load speed is
controlled by a patented algorithm that permanently optimises the
condensation/evaporation temperature to ensure the best unit
energy eciency (EER/COP) whatever the operating conditions
and pressure drop of the duct network.
If required by a specic installation, the unit's maximum fan speed
can be congured in the Service Conguration menu. Refer to the
control manual.
The maximum congured speed applies to both the cooling and
heating modes.
The performances (capacity, eciency, noise level) depend on
the fan speed and the duct network. Please refer to the
manufacturer's electronic catalogue to evaluate the estimated
impact of the ducting system on the unit's operating conditions.
12.2.7.1 - Specic installation in ductable units
The rotation speed of all the fans in the same circuit is controlled
in the same way.
Therefore each circuit operates independently.
Each refrigerant circuit must have an independent network of ducts
to prevent any recycling of air between the air-cooled exchangers
of dierent refrigerant circuits.
On ductable units, each fan is equipped with a factory-tted
connection interface frame providing a link between the duct
network itself and the refrigerant circuit to which the fan belongs.
Refer to the dimensional plans of the units for the precise
dimensions of this connection interface.
Please refer to the chapter ‘‘Arrangement of fans’’ to assign each
fan to their own circuit.
Specic data 30RQP
IMPORTANT: When the 30RQP units operate in heating mode,
dehumidication of the air and defrosting of the air heat
exchangers generate a large amount of condensate that must
be evacuated from the unit installation site.
30RQP units must be installed on a waterproof base enabling
ecient drainage and evacuation of the condensate from the
exchangers.
At low ambient temperature, when the exchangers form frost,
the defrost water must be collected to ensure that there is no
risk of ooding of the area where the units are installed.
12.2.7.2 - Nominal and maximum air ow rate per circuit
and per unit type
30RBP
Rated air ow
rate
(1)
(l/s)
Maximum air ow
rate
(2)
(l/s)
170R 13500 20160
190R 18220 26880
210R 18110 26880
230R 18010 26880
270R 17770 26880
310R 22370 33600
340R 22180 33600
380R 26810 40320
410R 26610 40320
450R 31230 47040
480R 31050 47040
550R 35490 53760
610R 39990 60480
670R 44470 67200
720R 44200 67200
770R 48710 73920
800R 48570 73920
870R 52970 80640
950R 52620 80640
30RQP
Rated air ow
rate
(1)
(l/s)
Maximum air ow
rate
(2)
(l/s)
165R 14010 18720
180R 13920 18720
210R 18700 24960
230R 18590 24960
270R 18490 24960
310R 23200 31200
330R 23080 31200
370R 27840 37440
400R 27700 37440
430R 32480 43680
470R 32320 43680
520R 36980 49920
(1) The rated air ow rate is set in accordance with Eurovent 12/7 - 35 °C, with an
operating pressure of 160 Pa.
(2) The maximum air ow rate corresponds to the maximum obtainable by these
fans (maximum speed, operating pressure = 0 Pa)
These values are given for illustrative purposes only. The actual and up-to-date
ow rates based on the condition are indicated via the selection on the electronic
catalogue.
12.2.7.3 - Air connection on discharge
Refer to the dimensional plans of the units for the precise
dimensions of the connection interface.
12 - OPTIONS
71