31
4.5 - Electrical data (continued)
30XB from 1100 to 1700 (continued)
30XB 1100 1200 1300 1400 1500 1550 1700
Maximum current (Un-10%)
(1)
Standard unit
Circuit 1
(a)
A 320 366 440 470 509 740 593
Circuit 2
(a)
A 466 509 470 505 509 370 593
Option 081 A 788 877 912 977 1020 1113
Unit + option 15LS
Circuit 1
(a)
A 309 355 424 454 491 727 574
Circuit 2
(a)
A 452 491 454 489 491 357 574
Option 081 A 762 848 880 945 985 1074
Nominal start-up current
(3)
Standard unit
Circuit 1
(a)
A 587 587 629 629 629 954 812
Circuit 2
(a)
A 629 629 629 629 629 477 812
Option 081 A 940 980 985 1015 1019 1316
Option 081 & Opt 25c A 802 820 844 862 862
Unit + option 15LS
Circuit 1
(a)
A 576 576 613 613 611 941 793
Circuit 2
(a)
A 615 611 613 613 611 464 793
Option 081 A 914 951 953 983 984 1290
Option 081 & Opt 25c A 776 791 812 830 826
Maximum start-up current(Un)
(2)
Standard unit
Circuit 1
(a)
A 587 587 629 629 629 954 812
Circuit 2
(a)
A 629 629 629 629 629 477 812
Option 081 A 1046 1095 1095 1130 1134 1431
Option 081 & Opt 25c 802 820 844 862 862
Unit + option 15LS
Circuit 1
(a)
A 576 576 613 613 611 941 793
Circuit 2
(a)
A 615 611 613 613 611 464 793
Option 081 1020 1066 1063 1098 1099 1393
Option 081 & Opt 25c A 776 791 812 830 826
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan current + locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XB1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS