34
4.5 - Electrical data (continued)
30XB from 250 to 1000 with option 254 or 255
30XB with option 254 or 255 250 300 350 400 450 500 600 700 750 800 850 900 1000
Power circuit supply
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V via internal transformer
Maximum operating input power
(1)
Standard unit kW 119 133 149 168 195 216 264 285 321 340 371 398 460
Unit + option 15LS kW 112 126 141 159 185 205 251 271 306 325 355 381 438
Power factor at maximum power
(1)
Standard unit
Displacement Power Factor (Cos Phi) 0,88 0,88 0,88 0,88 0,89 0,89 0,89 0,89 0,89 0,89 0,89 0,90 0,90
Unit + option 15LS
Displacement Power Factor (Cos Phi) 0,88 0,88 0,88 0,88 0,89 0,89 0,89 0,89 0,89 0,89 0,89 0,90 0,90
Nominal operating current draw
(2)
Standard unit A 151 167 185 210 239 270 324 349 405 433 452 520 550
Unit + option 15LS A 141 157 174 197 226 256 306 330 385 413 431 498 525
Maximum operating current draw (Un)
(1)
Standard unit A 198 220 245 278 319 352 430 464 522 552 601 643 743
Unit + option 15LS A 188 210 234 265 306 338 412 445 502 532 580 621 717
Maximum current (Un-10%)
(1)
Standard unit A 198 220 245 278 319 352 430 464 522 552 601 643 743
Unit + option 15LS A 188 210 234 265 306 338 412 445 502 532 580 621 717
Nominal start-up current
(3)
Standard unit A 246 246 264 379 479 482 535 561 737 760 766 852 866
Unit + option 15LS A 245 245 263 378 480 481 536 562 738 761 765 851 871
Unit + option 25C A 213 224 224 346 442 442 492 492 676 691 691 733 756
Maximum start-up current(Un)
(2)
Standard unit A 274 274 295 407 510 513 583 616 785 815 818 911 960
Unit + option 15LS A 264 264 284 394 497 499 565 597 765 795 797 889 935
Unit + option 25C A 213 224 224 346 442 442 492 492 676 691 691 733 756
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan current + locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS