33
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
4.5 - Electrical data (continued)
30XBP from 1100 to 1500 (continued)
30XBP 1100 1200 1300 1400 1500
Maximum current (Un-10%)
(1)
Standard unit
Circuit 1
(a)
A 313 359 430 460 498
Circuit 2
(a)
A 457 498 460 495 498
Option 081 A 772 859 892 957 998
Unit + option 15LS
Circuit 1
(a)
A 306 352 420 450 487
Circuit 2
(a)
A 448 487 450 485 487
Option 081 584 630 657 702 736
Nominal start-up current
(3)
Standard unit
Circuit 1
(a)
A 580 580 619 619 618
Circuit 2
(a)
A 620 618 619 619 618
Option 081 A 923 962 965 995 997
Option 081 & Opt 25c A 786 801,5 824 841,5 839,5
Unit + option 15LS
Circuit 1
(a)
A 573 573 609 609 607
Circuit 2
(a)
A 611 607 609 609 607
Option 081 A 907 944 945 975 975
Option 081 & Opt 25c A 770 783,5 804 821,5 817,5
Maximum start-up current(Un)
(2)
Standard unit
Circuit 1
(a)
A 580 580 619 619 618
Circuit 2
(a)
A 620 618 619 619 618
Option 081 A 1030 1077 1075 1110 1112
Option 081 & Opt 25c A 786 801,5 824 841,5 839,5
Unit + option 15LS
Circuit 1
(a)
A 573 573 609 609 607
Circuit 2
(a)
A 611 607 609 609 607
Option 081 A 1014 1059 1055 1090 1090
Option 081 & Opt 25c A 770 783,5 804 821,5 817,5
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan current + locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XBP1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.