BACview® system screens
BACview® CARRIER CORPORATION ©2021
Installation and User Guide All rights reserved
22
Screen
Description
BACnet
Time
Master
For: RTU Open and WSHP
Navigate to: System Settings > TimeMstr
For: i-Vu® Open Router
Navigate to: TimeMstr
The network should have only one BACnet Time Master that issues time broadcasts.
Set Time Sync Mode to:
No Broadcast if this controller is not the BACnet Time Master.
Local Broadcast to have the controller send time broadcasts only to controllers on his
locally connected MS/TP network.
Global Broadcast to have the controller send time broadcasts to all controllers and all
MS/TP networks in the system.
Set Time Sync Interval to how often the time broadcast should be sent (1-9999 minutes).
Local
Schedule
For: RTU Open, WSHP, VVT Zone, and VVT Bypass controllers
Navigate to: Config > Sched
See Setting local schedules (page 23).