Wiring the Carrier® Connect™ Wi-Fi Thermostat
   
 
 
 
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX    CARRIER CORPORATION ©2021  
Installation Guide    All rights reserved 
  11 
 
To wire hotel systems 
 
 
 
 
 
 
 
To wire for BACnet communication 
NOTE  Use the specified type of wire and cable for maximum signal integrity. 
 
22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire 
2000 feet (610 meters) per segment 
9600 bps, 19.2 kbps, 38.4 kpbs, or 76.8 kbps, 115.2 kbps 
 
 
Connect communication wiring to terminals A+ and B-. Do not terminate shield at the thermostat.  
 CAUTION  Maintain the same polarity. 
 
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.