Faults and system events
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION ©2021
Installation Guide All rights reserved
51
The faults and system events are displayed in the home and dormant screen banners. Faults and system events
include:
Startup
Software Update Events
Power Cycle Events
Parameter Out-of-Range Events
Server Connectivity Events
Non-Volatile Memory Faults
Temperature Faults
The Faults and System events display in the banner while fault condition exists. You can see a history of the faults
and system events in Carrier Connect mobile app under Alerts. The history is comprised of the 5 most recent
logged items, with the most recent event being listed at the top.
Faults
ID TEMP SENSOR HIGH
Fault becomes active when main thermistor (P102 or RT1) reads > 100°F.
Fault is cleared when temperature <= 99°F.
When this fault occurs, the thermostat uses the temperature reading from the
temperature/humidity sensor as the space temperature.
ID TEMP SENSOR LOW
Fault becomes active when main thermistor (P102 or RT1) reads < 39°F.
Fault is cleared when temperature >= 4°F.
When this fault occurs, the thermostat uses the temperature reading from the
temperature/humidity sensor as the space temperature.
REMOTE SENSOR HIGH
Remote temperature > 122°F; only flagged if remote sensor set to use as
indoor temperature (REMOTE SENSOR setting set to INDOOR or AVERAGE)
REMOTE SENSOR LOW
Remote temperature = 0°F; only flagged if remote sensor set to use as indoor
temperature (REMOTE SENSOR setting set to INDOOR or AVERAGE)
ID TEMP RANGE HIGH
If the mode is cooling (Cool or Auto operating in Cool), the space temperature
is greater than the cool setpoint plus the Maximum Setpoint Error and this
condition exists for the number of minutes specified by the INDOOR TEMP
FAULT INHIBIT time.
ID TEMP RANGE LOW
If the mode is heating (HEAT, EHEAT or AUTO operating in HEAT), the space
temperature is less than the heat setpoint minus the Maximum Setpoint Error
and this condition exists for the number of minutes specified by the INDOOR
TEMP FAULT INHIBIT time.
HUM SENSOR FAILURE
Humidity sensor timed out
humidity reading is > 99%
humidity reading is 0%.
HUMIDITY RANGE HIGH
Humidity reading is > 90%
Faults and system events